DCS modular data center

2026-01-09

Latest company case about DCS modular data center

latest company case about [#aname#]

Single cabinet dimensions (H*W*D):2000mm*600mm*1100mm

IT rated power:IT rated power≤4.5kW

Power supply:220V、230V、240V/50(60)Hz;208V(double live wire)/50(60)Hz

External interface:Local standard power interface

Operation condition:Temperature of 5℃ to 30℃, relative humidity of 10% to 90%, altitude of 0m to 3000m

Structure:Single front door and double rear doors with 110 degree Opening angle

Heat dissipation:The speed of intelligent fans at top of the cabinet is adjusted in real time according to the temperature in order to save energy.

Air flow:70% door open ratio, Front-back air flow pattern, Optional cooling module at the top of cabinet

Power distribution:Various efficient UPSs with different backup time for option, C-class lightning protection and manual maintenance bypass UPS

Monitoring system:Running information collection and management of cabinet microenvironment, UPS, power distribution equipment and fan control system, supporting remote management and unified control with SMS notification.

Installation type:Coupled with wheels and leveling feet

latest company case about [#aname#]

Single cabinet dimensions (H*W*D):2000mm*600mm*1200mm

IT rated power:IT rated power≤5.0kW

Power supply:220V、230V、240V/50Hz

External interface:Local standard power interface

Operation condition:Temperature of 5℃ to 45℃, relative humidity of 20% to 90%, altitude of 0m to 3000m

Structure:The top of front door is sealed with glass, and the bottom is perforated, rear doors are double perforated.

Heat dissipation:Intelligent air conditioner automatically runs between fan and compressor mode according to the ambient temperature for energy saving.

Air flow:Professional air guide components at the bottom of the front and rear doors to meet precision cooling.

Power distribution:Various efficient UPSs with different backup time are optional.

Monitoring system:Running information collection and management of cabinet microenvironment, UPS, power distribution equipment and fan control system, supporting remote management and unified control with SMS notification.

Installation type:Coupled with wheels and leveling feet

latest company case about [#aname#]

Miro data center has sn integrated monitoring platfor to collect, manage,analyzeand warn the environment and equipment operation information in the cabinet, UPS, power distribution system mornitoring, fan control system monitoring. On-site and remote web interface monitoring for remote operation of single site. It can also be equipped with miro data center infrastructure management system to achieve centrlized morntoring and unified management of multiple sites.

Note:

For the configuration, UPS backup is 1+1.

"× "stands for no configuration, "√" stands for standard configuration. Switch, router or sever are not mandatory, and will be provided by customers.

All above six configurations are designed based on condition of the maximum heat emission (3kW).

Main cabinet standard configuration: One set of PDU, monitoring module, smoke detector, temperature and humidity sensor, water sensor, door magnetic switch.

Network cabling cabinet standard configuration: One set of PDU, smoke detector and door magnetic switch.

Battery cabinet standard configuration: One set of smoke detector and door magnetic switch.